What Is Zs in Electrical Testing?
What Zs means, how it differs from Ze, and why a reading needs context.
Written by
TestFast Team
Electrical testing software built by electricians, for electricians
Zs is the earth fault loop impedance measured at the furthest point of the circuit under test. It describes the impedance of the fault-current loop from the origin, out along the circuit and back.
The number matters because, under automatic disconnection of supply (ADS), the protective device must disconnect within the required time. The relevant maximum Zs depends on the protective device and its characteristics. There is no single “good Zs” number that applies to every circuit.
Here is what Zs tells you, how it differs from Ze, and what to check before comparing a reading with a maximum value.
Quick summary
- Zs is the earth fault loop impedance for the circuit at the point being assessed, normally its most distant point.
- Ze is the external, supply-side part of the loop. Zs also includes the circuit’s contribution.
- A calculated value can be expressed as Zs = Ze + (R1 + R2).
- A Zs result only makes sense when you know the circuit, protective device and comparison basis behind it.
- Do not treat a bare reading as a universal pass/fail answer.
What does Zs mean?
Zs means earth fault loop impedance. In the definition used by the IET, measured Zs is the impedance of the earth fault current loop up to the most distant point of the relevant circuit from its origin.
In plain terms, it is the impedance around the path fault current would take from the supply, through the circuit and back. It is not just a reading for the supply or the cable on its own.
Ze and Zs are not the same reading
Ze is the external part of the loop on the supply side. The circuit adds its own contribution, represented in the calculation by R1 + R2. That is why the calculated relationship is:
Zs = Ze + (R1 + R2)
A Ze result and a circuit Zs result answer different questions. Comparing Ze directly with a circuit’s maximum Zs can put the wrong values against each other.
Why is Zs checked?
Under ADS, the protective device must disconnect within the required time for the circuit and earthing arrangement. Checking the Zs result against the applicable maximum is one way to confirm the disconnection requirement is met.
The comparison is device-dependent. The protective device and its characteristics matter, and manufacturer data may govern where available. Required disconnection time also varies with the supply voltage, earthing arrangement and whether the circuit is a distribution circuit or a final circuit. So a general-purpose Zs table or rule of thumb cannot replace checking the right basis for the circuit.
Measured Zs and calculated Zs
A Zs value may be measured at the circuit, or calculated from Ze and R1 + R2. These are different routes to a value, not a reason to assume two figures will always match exactly.
The comparison basis matters too. BS 7671 Chapter 41 table values are stated for full-load operating temperature. Conductor resistance rises with temperature, so a design-condition table value and a value used to compare a measured result are not interchangeable without accounting for the basis being used.
If a result looks marginal, check what was measured or calculated and which maximum value it is being compared against. Do not quietly switch between a design value and a measured-result comparison value.
What is a “good” Zs reading?
There is no universal answer. The applicable maximum depends on the protective device and its characteristics, and the comparison has to use the correct basis for the result.
A number on its own does not tell you whether the circuit meets the relevant requirement. Before drawing a conclusion, identify the circuit and device, confirm whether the figure is measured or calculated, and establish the applicable comparison value. Use manufacturer data where it applies.
For the relevant maximum values and comparison context, see TestFast’s guide to earth loop impedance test values, maximum permitted Zs, and the max Zs calculator. The calculator is a lookup aid, not a substitute for selecting the correct device and basis.
Common Zs mistakes
- Treating Ze as Zs. Ze is the external contribution; Zs includes the circuit path being assessed.
- Using one “good” number for every circuit. The applicable maximum depends on the protective device and its characteristics.
- Comparing values without stating the basis. Design-condition and measured-result comparison values are not automatically interchangeable.
- Calling a reading a pass or fail without context. First establish the circuit, device, method and relevant comparison value.
- Assuming a calculated figure is a direct measurement. Keep clear which route produced the value and what inputs it depends on.
What to make clear when recording a result
When you record or review a Zs figure, make its context clear: which circuit it relates to, whether it was measured or calculated, and what maximum or comparison basis you used. That makes the number easier to interpret later and avoids presenting it as a standalone verdict.
For wider certificate workflow, see TestFast EICR software. A reporting tool can help capture information clearly; it does not decide whether an installation is safe or replace competent assessment.
The short version
Zs is the earth fault loop impedance for the circuit up to the point being assessed. Ze is only the external part; the circuit contributes too. Zs is checked in the context of ADS and the protective device, but the right comparison depends on the circuit and the basis used. Get those details straight before calling a reading good, bad or compliant.
For the technical basis, see the IET explanation of maximum earth fault loop impedance and protective devices and its guide to why maximum earth fault loop impedance values differ.